
Parameter Dictionary Parameters
Regen Resistor Status. Bit-mapped as follows:
Set if the regen circuit is currently closed.
1 Set if regen is required based on bus voltage.
Set if the regen circuit is open due to an overload condition. The overload may be caused by
either the resistor settings or the internal drive protections.
3-15 Reserved.
Position Loop Output Gain Multiplier. The output of the position loop is multiplied by
this value before being passed to the velocity loop. This scaling factor is calculated
such that a value of 100 is a 1.0 scaling factor.
This parameter is most useful in dual loop systems.
Maximum Current to use with algorithmic phase initialization. See code 5 of
Commutation Mode (0xB2). Units: 0.01 A.
Algorithmic Phase Initialization Timeout. See code 5 of Commutation Mode (0xB2).
Units: ms.
Maximum Velocity Adjustment. This is the maximum velocity adjustment made by the
stepper outer position loop when enabled. This parameter is only used when the
stepper outer loop is engaged (when bit 1 of Stepper Configuration & Status (0xEE)
is set). Units: 0.1 steps/s.
Proportional Gain For Stepper Outer Loop. This parameter gives the gain used for
calculating a velocity adjustment based on Position Loop Error (0x35). This
parameter is only used when the stepper outer loop is engaged (when bit 1 of
Stepper Configuration & Status (0xEE) is set).
Holding Current For Microstepping Mode. Units: 0.01 A.
0xE9 0xEA 0x4E9 0x21D1 RF U16 Run to Hold Time For Microstepping Mode. Units: ms.
Detent Correction Gain Factor For Microstepping Mode.
Holding Current To Fixed Voltage Output Time for Microstepping Mode. Time delay
from entering hold current before entering the special voltage control mode of
operation. This mode trades the normal tight control of current for very low jitter on
the motor position. Used in stepper mode only. Set to 0 to disable this feature. Units:
ms.
Copley Controls Page 48
Komentarze do niniejszej Instrukcji