Parameter Dictionary Parameters
referenced (i.e. homing has been successfully completed). Set to greater than
positive software limit to disable. Units: counts.
0xBA 0xBB 0x4BA 0x2120 RF INT32 Position Tracking Error Limit. Also known as Tracking Error Window. If the Position
Loop Error (0x35) exceeds this value then the tracking error bit (bit 18) of the Drive
Event Status Register (0xA0) is set and the motor is stopped. Using Fault Mask
(0xA7), the tracking error event can be configured to either disable the drive
immediately, or abort the present move and continue holding position. Units: counts.
Position Tracking Warning Limit. If the Position Loop Error (0x35) exceeds this value
then the tracking warning bit (bit 19) of the Drive Event Status Register (0xA0) is set.
Units: counts.
Position Tracking Window Limit. If the Position Loop Error (0x35) exceeds this value
then the tracking window bit (bit 25) of the Drive Event Status Register (0xA0) is set.
Units: counts.
Time Delay For Position Tracking Error Limit (0xBA). The tracking window bit (bit 25)
of the Drive Event Status Register (0xA0) will not be cleared until the Position Loop
Error (0x35) has been within the Position Tracking Error Limit (0xBA) for at least this
long. Units: ms.
Software Limit Deceleration. The deceleration rate used to stop a motor when
approaching a software limit. Units: 10 counts/s
2
.
Homing Current Delay Time (used with home to hard stop mode only). When
performing a home to hard stop, the amplifier will push against the stop for this long
before sampling the home position. Units: ms.
Network Node ID. This is the drive’s present ID as read at system startup. The node
ID is only read at system startup, so this value will not change unless the drive is
reset. See Network Node ID Configuration (0xC1).
Network Node ID Configuration. Defines how a drive’s node ID is calculated, and
specifies the drive’s network bit rate.
The ID is calculated at startup (and only at startup) using a combination of general-
purpose input pins and a programmed offset value. On certain models, an address
switch is also used. The resulting value is clipped to a 7-bit ID in the range 0 to 127.
Bit-mapped as follows: